The effect of changing the type of lamp, lighting power and adding light points to the strength of the lighting in the Classroom and Reading Room of the Postgraduate Program at the Bung Hatta Building, Universitas Negeri Jakarta
Massus Subekti 1*), Imam Arif Rahardjo 2), Eka Mardiana 3)

1), 2), 3) Electrical Engineering Faculty of Engineering, Universitas Negeri Jakarta
Jalan Rawamangun Muka, Jakarta 13220, Indonesia
* Correspondence : masus[at]unj.ac.id


Abstract

This research was conducted to determine the effect of changing the type of lamp, the addition of power and the number of lighting points to the strength of lighting in the Classroom and Reading Room of the Postgraduate Program at the Bung Hatta Building, Universitas Negeri Jakarta. This research was conducted because the room has strong lighting that is too large during the day and too low at night. This research uses a quantitative approach with a descriptive engineering method through three stages of engineering namely manual measurement using Luxmeter, manual calculations based on SNI standards and simulations. The results showed that when the treatment has not been done, the average value of the measured illumination and based on the simulation results in the reading room (6th floor) and lecture room (7th and 8th floor) do not meet SNI 03-6197: 2011 Standards. Through changing the type of lamp, the addition of power and the number of points there are 15 rooms that meet the standards with an average optimization presentation of 20% to 88%.

Keywords: strong lighting, classroom, lamp type, lamp type.